Phone 651-426-9085
800-MLC-8020
Fax 651-426-9354
|
 |
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
UL 508A Industrial Control Panels
|
| |
P U M P M A S T E R
Master Pump Controller
MPC-300-1
|
|
The Master Pump Controller is a pressure controller which senses level of a tank or sump
and controls one or two pumps. The Master Pump Controller provides level setpoint control
from any tank transducer with a 4-20ma output. The transducer needs to be located to
measure static pressure only. Avoid transducer locations with pumping surges. The Master
Pump Controller has 4 function keys, 1 system test key, and a enter key. The operator
selects the pump setpoint display and inputs level start and stop setpoints, alternation
features, and high and low alarm set points.
The Pump Controller has a isolated 24VDC power supply for the 1 analog input. The controller
can be setup for pump up (pump in) or pump down (pump out) operation. The transducer can be
mounted in the enclosure or be remote. The controller can be easily configured for sewage lift
stations, ground water storage tanks, and elevated tanks with a pressure tap on the riser. The
operator can force a complete system test and check on all set points and outputs. Unit has
built in pump running time counters easily displayed from a front panel button. High and low
alarm indicators. Front panel pump 1 and pump 2 seal failure and high temperature indicators.
Pump hand-off-auto control switches are provided for each pump. Pump output relays are
provided and are rated 10 amp @ 120/230v.
|
|